Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)8 4 x 4 electrical box in machine room ceiling needs to have wiring inside box and cover installed. 9/1/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log A monthly record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. 7/14/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log MCP Fire service testing must be properly documented monthly on log sheet. 9/1/2023