MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Provide testing of shunt trip disconnect activated by the machine room heat detector
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
|
|
Provide current and up to date prints in the machine room
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Door closing device shall close door when the elevator is not at the landing
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher dated 2017. Provide a Fire extinguisher with a current service date
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide maintenance logs
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Provide maintenance control program
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self closing and self locking
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing in car handrail
|
|
MO Minimum : Elevators
|
11 CSR 40-5.130 Variances
|
(2)(B) Variance Inspection
|
|
|
Required Variance Inspection required
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove compressor from elevator Machine Room - Blocking entrance
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
All water and gas conveying devices shall be separated from the elevator machine room
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lighting shall be 10ft candles through out. Measured at the floor
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove cable equipment from the elevator machine room
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Provide testing of shunt trip disconnect activated by the machine room heat detector
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
|
|
Provide current and up to date prints in the machine room
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Door closing device shall close door when the elevator is not at the landing
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher dated 2017. Provide a Fire extinguisher with a current service date
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide maintenance logs
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Provide maintenance control program
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self closing and self locking
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replacement Parts::Replace missing in car handrail
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Need to replace missing handrail
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove compressor from elevator Machine Room - Blocking entrance
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
All water and gas conveying devices shall be separated from the elevator machine room
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lighting shall be 10ft candles through out. Measured at the floor.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove cable equipment from the elevator machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Provide a 5gal maximum container in the pit to collect packing leakage
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Connect fire alarm initiating devices to the elevator controller
|
5/11/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair inoperative emergency phone
|
5/11/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Connect fire alarm initiating devices to the elevator controller
|
2/27/2024
|