Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current State operating permit shall be obtained and displayed in the equipment room.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Fire service operation shall be tested monthly and documented on fire service testing log. No log present.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Adjust upthrust roller bearings for proper clearance to door hanger track (all floors).
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Compliant/required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, & evacuation procedures. No documentation found for 2022 through 2025.
conversion conversion n/a Replace missing gib on 1st & 3rd floor hoistway door 12/2/2019
MO Minimum : Elevators (H) - Machine Rooms (H)1 Post current state certificate in machine room 12/2/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No current state operating certificate on display in machine room. 11/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Maintenance control program shall include written procedures for inspections and tests on site. 11/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor does not work. 2/2/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 6/14/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Victraulic fitting below valve assembly is bad, repair as needed. 6/14/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Selector rope tail sheave in the pit excessively noisy. 6/14/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) None 6/14/2024
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 x OSV in the pit is due for testing, provide. 4/28/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x Victaulic fitting below valve assembly is bad, repair as need. This violation was previously marked as "fixed" in the database but was not. As of 4/28/25, fitting is severely spraying high pressure hydraulic fluid. Red Tag Issued. 5/21/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work. No dial tone. 5/21/2025