Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)1 No No Complete annual test within 30 days 7/20/2020
MO Minimum : Elevators (I) - Pits (I)1 No No Remove oil from pit floor 7/20/2020
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Remove oil from machine room floor pump unit 7/20/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State certificate in machine room 7/20/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No No current operating certificate on display in machine room. 11/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Maintenance control program shall include written procedures for inspections and test located on site. 11/1/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No None 8/9/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove oil from Machine room floor. Pump moter drip pan 7/20/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 8/9/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current State operating permit shall be obtained and displayed in the equipment room. 5/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Compliant/required documentation shall be kept in the equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, & evacuation procedures. No documentation found for 2022 through 2025. 5/16/2025
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Fire service operation shall be tested monthly and documented on fire service testing log. No log present. 5/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Adjust upthrust roller bearings for proper clearance to door hanger track (all floors). 5/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Provide existing emergency lights to work 4/29/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) Yes No Repair door restrictors on front & rear car door 2/20/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency lights not working, repair. Bell ok. 4/25/2022