Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) An annual test tag needs to be provided attached to each controller
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) The on-site maintenance records need to be updated for 2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency alarm bell shall work. 7/31/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In cab emergency light shall work. 7/19/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 x Machine room disconnecting means shall be provided with a compliant mechanical auxiliary contact to disconnect the load from the auxiliary power supply. 7/20/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x "A" floor lobby smoke sends elevators to ALT floor, instead of primary recall. Need to reprogram and retest all device recall operations. 7/20/2023