Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x "A" floor lobby smoke sends elevators to alternate floor, instead of primary recall. 7/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) An annual test tag needs to be provided and attached to the controller
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Battery lowering was tested and working, but mainline disconnect microswitch failed to operate. 7/6/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Battery lowering was tested and working, but mainline disconnect microswitch failed to operate. 7/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) The on-site records need to be updated for 2025
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Ventilation grill cover shall be reinstalled in the machine room. 7/6/2023