Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Ceiling panels in car are open crate type, providing no protection for passengers in event of a bulb breakage. Replace panels with solid type or install plastic tubes and endcaps over bulbs. 8/28/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Car top lighting inoperable and shall be repaired. 10/15/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current state operating certificate shall be displayed in elevator machine room. 10/15/2025
A17.1-2016 : Elevators 1.3 - Operating control devices 8.10.2.2.1(c) No No The down inspection button on the car top shall be made operational
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Means of two-way communication are inoperable and shall be repaired, or replaced. 10/15/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working. Re-inspection required 8/18/2023