Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x 8.10.2.3.2(m) There were new smoke and heat detectors installed in the elevator machine room and hoistway. An alteration permit needs to submitted to the Department of Elevator Safety. They may require an acceptance inspection for the new fire alarm initiating devices. 7/23/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary lowering shall activate only when there is a failure of the main building power. Auxiliary lowering is activating when the disconnect is pulled.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The Emergency Light and Bell do not work when normal power is removed
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 8/31/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Replace the missing hoistway door pick-up rollers at 1st and 2nd floor. 8/31/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Telephone in car doesn't work. (Dials then hangs up) 8/18/2022