MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Telephone in car doesn't work. (Dials then hangs up)
|
8/18/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
8/31/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Replace the missing hoistway door pick-up rollers at 1st and 2nd floor.
|
8/31/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
8.10.2.3.2(m) There were new smoke and heat detectors installed in the elevator machine room and hoistway. An alteration permit needs to submitted to the Department of Elevator Safety. They may require an acceptance inspection for the new fire alarm initiating devices.
|
|