MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
|
|
DOOR CLOSING FORCE IS >30
|
8/14/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.16.8
|
x
|
|
Driving machine does not safely lower and stop elevator with 125% of rated load on the elevator.
|
9/23/2020
|
MO Minimum : Elevators
|
(G)2-Alterations
|
8.7.2.14.2 Car Enclosure
|
x
|
|
Emergency light and bell do not operate.
|
6/4/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Fire hat inside elevator does not flash when machine room fire alarm initiating device is activated.
|
9/23/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
Install dust covers on all 12 hoistway door hangers. Dustcovers are laying on top of the elevator.
|
6/28/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)6
|
|
|
Mark governor with identification number #2
|
8/10/2021
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.6.4.20.10
|
x
|
|
Perform 125% brake test
|
7/19/2021
|
A17.1-2016 : Elevators
|
2.29 - Car and counterweight safeties
|
8.6.4.20.1
|
x
|
x
|
Perform full load safety test
|
7/19/2021
|
A17.1-2016 : Elevators
|
2.29 - Car and counterweight safeties
|
8.6.4.19.2
|
x
|
x
|
Perform no load safety test. Elevator is past due for annual safety testing.
|
9/23/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(d)(1)
|
|
|
Post emergency evacuation of passengers procedure in machine room
|
8/10/2021
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.20.2
|
x
|
|
Test tripping speed of governor and forces of pull thru
|
7/19/2021
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
8.6.4.20.11 (Re-Inspection)
|
x
|
|
Test unintended motion in down direction with 125% of rated load
|
7/19/2021
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
8.6.4.20.11 (Re-Inspection)
|
x
|
x
|
Unintend motion down test exceeded 48 inches. Elevator car sill stopped 76 inches below the landing sill.
|
8/9/2021
|