Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.40 - Maintenance Records 2.26.1.4 Inspection Operation 8.6.4.9 - Clean the car top. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops 8.6.4.9 - Clean the car top. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service test charts are missing. 12/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 5/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) All machine room wiring shall be enclosed. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) All machine room wiring shall be enclosed. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Clean the pit. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Clean the pit. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) Hoistway ducts shall have covers installed 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) Hoistway ducts shall have covers installed. 9/10/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door closer may need to be adjusted.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys (Re-Inspection) x Phase 1 fire service key switch shall be operational in the firemans command panel. 3/5/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post the current state operating certificate in the elevator machine room 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post the current state operating certificate in the elevator machine room. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.7.1.8 Provide a code compliant code data tag. 5/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including onsite documents. 5/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.7.1.8 Provide a code data plate on the controller, and include any information pertaining to the major alteration. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.7.1.8 Provide a code data plate on the controller, and include any information pertaining to the major alteration. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 2.18.5 Provide a governor rope tag. 5/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) x x Provide code compliant counterweight runby. 1/27/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Provide code compliant pit lighting (10 ftc). 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Provide code compliant pit lighting (10 ftc). 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Provide code compliant pit lighting. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 2.18.5 Provide governor rope data tag 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 8.7.2.19 Provide governor rope data tag. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide MCP documentation 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide MCP documentation. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) Provide numbering of car top 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) Provide numbering of car top. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.26 - Broken rope, chain, or tape switch 8.11.2.1.3(i) x x Replace the broken tape switch in the pit and ensure the tape switch is mounter properly. 1/27/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) Replace the missing cover on the electrical junction box (utility) at the top of the hoistway. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) Replace the missing cover on the electrical junction box (utility) at the top of the hoistway. 9/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 The machine room door shall be self-closing and self-locking. 12/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) The machine room door shall be self-closing and self-locking. 5/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) The main disconnect shall be labeled with the source location, name, and breaker numbers. 5/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) x The suspension ropes are undersized and have excessive wear. The suspension ropes shall be replaced. 5/8/2023