Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current operating certificate shall be displayed in machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.7.2.21 x All hoist rope sheave guards shall be checked and adjusted for proper operation. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 8.10.2.2.5(c) x Car and counterweight buffers shall be tested. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.10 - Compensating chains, ropes, and sheaves 8.11.2.1.5(h) x Compensation ropes shall be equally tensioned. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 8.10.2.2.5(c) x Counterweight comp rope bracket shall not contact comp sheave when counterweight buffer is fully compressed. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) x Door closing force shall be tested. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x If the emergency communication means is normally connected to the building power supply, it shall automatically transfer to a source of standby or emergency power as required by the applicable building code. The power source shall be capable of providing for illumination of the visual indication within the car, and the means of emergency communications for at least 4 hours; and the audible signaling device for at least 1 hour. 11/16/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Install cover on the car top control box. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Install duct covers on wire raceway at top of hoistway. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.18.7 x Install hoist rope data tag. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) x Patch holes where prior direction arrows were located on various floors. 6/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Patch holes where prior directional arrows were located on various floors.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x Phase 1 fire service shall be tested, as well as, all initiating devices. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 2.26.1.1 x Properly secure the car operating panel. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.9 x Provide a code compliant code data tag. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 x Provide a code compliant MCP including onsite documents. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Remove unused junction box in the hoistway.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.11.2.1.5(j) x The car safeties shall be tested. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 x The machine room door shall be self-closing and self-locking. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x The tape switch electrical box shall have a cover installed. 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Unused wire raceway and junction box shall be removed from the hoistway. 6/28/2022