Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.16.8 Yes No The drive machine brake shall be tested.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.19 - Car Ride 2.23 Yes No Verify that the car levels properly with all floors.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 2.26.1.1 Yes No Properly secure the car operating panel cover.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 2.26.12 Yes No Patch holes where prior direction arrows were located on various floors.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.26.2.7 Yes No The pit stop switch shall be located approximately 18" above floor level and adjacent to the pit ladder.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.26.2.7 Yes No The pit stop switch shall have a cover installed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes All phases of fire service shall be tested, as well as, all initiating devices.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Yes No The machine room door shall be self-closing and self-locking.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Yes No The machine room lighting shall be 10 foot-candles at the floor level.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 8.10.2.2.5(c) Yes No Car and counterweight buffers shall be tested.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No 2.12.3 - There is insufficient work space in front of the controller. Currently 33" to other controller and 21" to MG set. The clearance shall be 48".
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The person receiving the emergency phone call from the elevator shall be able to identify the location the call is originating from.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) Yes No Door closing force shall be tested.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) Yes No Patch holes in the hoistway at 6th & 28th floors.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.11.2.1.5(j) Yes No The car safeties shall be tested.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Yes No Provide a code compliant MCP including onsite documents.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches Yes No The bottom hoistway access switch shall limit movement to the point where the bottom of the platform guard is even with hoistway entrance.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Yes No Materials not used for operation of elevators shall not be in the machine room. (Non used controllers, MG sets, and various items)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.9 Yes No Provide a code compliant code data tag.