ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In cab emergency telephone shall work with 24/7 support.
|
1/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
3/5/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
10/6/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
Machine room door shall be self-closing.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
The machine room door shall be self-closing.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
Machine room door shall be self-closing.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
The lighting in the machine room shall be guarded to prevent breakage or accidental contact.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.3.1.2(c)
|
|
|
The machine room lighting shall be operational.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.3.1.2(c)
|
|
|
The lighting in the machine room shall be guarded to prevent breakage or accidental contact.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.3.1.2(c)
|
|
|
The machine room lighting shall be operational.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide a code compliant MCP including onsite documents.
|
5/3/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Monthly fire service test charts are missing.
|
12/19/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
Provide a code compliant fire extinguisher in the elevator machine room.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
The fire extinguisher in the machine room is expired and shall be replaced or serviced.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
The fire extinguisher in the machine room is expired and shall be replaced or serviced.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2 (Re-Inspection)
|
x
|
|
Pipes carrying liquids in proximity to the pump unit shall be guttered or guarded.
|
11/16/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Clean the pit.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Clean the pit.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Provide code compliant pit lighting.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
Provide code compliant pit lighting.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.11 - Plunger and Cylinder
|
3.18
|
|
|
Scavenger lines shall be repaired and completed.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.11 - Plunger and Cylinder
|
3.18
|
|
|
Scavenger lines shall be repaired and completed.
|
11/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6
|
x
|
|
Phase 2 fire service shall operate properly. (Completed March 5th)
|
3/5/2020
|
conversion
|
conversion
|
n/a
|
|
|
Pit light shall work and provide a minimum of 5 foot candles at the pit floor.
|
11/10/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
In cab emergency telephone shall work on battery power.
|
1/9/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be displayed in the elevator machine room.
|
5/3/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display a current MO State operating certificate in the machine room.
|
12/19/2022
|