Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Provide MCP.
MO Minimum : Elevators (I) - Pits (I)1 Remove oil from the sump hole.
MO Minimum : Elevators (I) - Pits (I)1 Determine if sump pump works, if not replace.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Provide guard on bulbs, to prevent accidental contact or breakage. Or change egg crate style ceiling in car.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Machine room ventilation fan has been removed, replace as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean the car top.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Car top inspection function not working, make so.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone needs to work. 6/24/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone. No active phone line. 5/13/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Perform OSV test on or before next annual inspection date. 5/13/2022
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x Unsealed. 5/13/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work on normal or emergency 110v power 5/13/2024