Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Provide guarding for lighting above machine. 8/20/2026
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No Provide a GFCI outlet in machine room. 8/20/2026
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No Provide a GFCI outlet in machine room. 9/20/2025
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No Provide a GFCI service outlet in machine room. 8/20/2026
MO Minimum : Elevators (I) - Pits (I)5 No No Secure pit ladder. 8/20/2026
MO Minimum : Elevators (I) - Pits (I)8 No No Provide a cover for sump pump in machine room/pit. 9/20/2025
MO Minimum : Elevators (I) - Pits (I)8 No No Provide a cover for sump pump in machine room/pit. 8/20/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Yes No Needs a pit ladder. 1/25/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Yes No Needs a pit light. 1/25/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 No No Provide feed source for main line disconnect. 9/20/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 No No Provide feed source for cab light disconnect. 8/20/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate in machine room. 9/20/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) No No Provide guarding for lighting above drive machine in machine room. 2.7.5.1 9/20/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) No No Provide guarding for lighting above drive machine in machine room. 2.7.5.1 8/20/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) No No Provide an HVAC system in machine room to keep temperature and humidity within ranges listed by manufacturer. 2.7.5.2 9/20/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) No No Provide and HVAV system in machine room to keep temperature and humidity within ranges listed by manufacturer. 2.7.5.2 9/20/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) No No Provide an HVAC system in machine room to keep equipment within safe operating ranges. 8/20/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) No No Main line disconnect not labeled with feed source. 2.26.4.1 9/20/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) No No Car light disconnect not labeled with feed source. 2.26.4.1 9/20/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide an MCP in machine room to log maintenance, repairs, and inspections. 9/20/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) Yes No Shorten ropes. 12/17/2024
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.19.3 Yes No Adjust governor rope tension device in pit. 12/17/2024