Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.19.3 x Adjust governor rope tension device in pit. 12/17/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) Car light disconnect not labeled with feed source. 2.26.4.1
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) Main line disconnect not labeled with feed source. 2.26.4.1
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 x Needs a pit ladder. 1/25/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Needs a pit light. 1/25/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room.
MO Minimum : Elevators (I) - Pits (I)8 Provide a cover for sump pump in machine room/pit.
MO Minimum : Elevators (I) - Pits (I)8 Provide a cover for sump pump in machine room/pit.
MO Minimum : Elevators (H) - Machine Rooms (H)7 Provide a GFCI outlet in machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)7 Provide a GFCI outlet in machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)7 Provide a GFCI service outlet in machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Provide an HVAC system in machine room to keep equipment within safe operating ranges.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Provide an HVAC system in machine room to keep temperature and humidity within ranges listed by manufacturer. 2.7.5.2
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide an MCP in machine room to log maintenance, repairs, and inspections.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Provide and HVAV system in machine room to keep temperature and humidity within ranges listed by manufacturer. 2.7.5.2
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Provide feed source for cab light disconnect.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Provide feed source for main line disconnect.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Provide guarding for lighting above drive machine in machine room. 2.7.5.1
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Provide guarding for lighting above drive machine in machine room. 2.7.5.1
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Provide guarding for lighting above machine.
MO Minimum : Elevators (I) - Pits (I)5 Secure pit ladder.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Shorten ropes. 12/17/2024