MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
did not find Maintenance Control Program (MCP) documents in the machine room
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
did not find monthly fire service test log in the machine room
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Need to perform and post monthly fire service test log in the elevator machine room
|
11/25/2019
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Provide a ABC fire extinguisher convenient to the access door
|
2/23/2021
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
provide a record of findings for firefighters' service operation.
|
2/23/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
The Maintenance Control Program (MCP) On-Site documents are not in the machine room.
|
1/3/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.7 Record of Oil Usage
|
|
|
the last entry on the oil record log is from 2018
|
1/3/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
The firefighters service test log is not being filled out monthly.
|
1/3/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
the next overspeed valve test is due in 2022
|
1/3/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)6
|
|
|
label the controller, tank, disconnect, car top, and pit Elevator #1
|
1/3/2022
|