Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Need to perform and post monthly fire service test log in the elevator machine room 11/25/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) do not store non-elevator related material in the machine room 11/25/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x provide working phone line to the elevator controller, the phone line that is there is dead. 7/27/2020
A17.1-2016 : Elevators 2.7 - Fire Extinguisher n/a Provide a ABC fire extinguisher convenient to the access door 2/23/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x backup battery failed to operate 2/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records The Maintenance Control Program (MCP) On-Site documents are not in the machine room. 1/3/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log The firefighters service test log is not being filled out monthly. 1/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage could not find an oil record log in the machine room 1/3/2022
MO Minimum : Elevators (H) - Machine Rooms (H)6 label the controller, tank, disconnect, car top, and pit Elevator #2 1/3/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing the next overspeed valve test will be due in 2022 1/3/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records could not find Maintenance Control Program (MCP) documents in the machine room
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log did not find monthly fire service test log in the machine room