Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)8 Car lighting disconnect in machine room requires a proprietary key which was not found in the room. Provide key to be left in machine room. 7/16/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In car emergency telephone shall work. 7/8/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Red Tag) x In cab emergency telephone does not work, and shall be repaired and retested. 6/12/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Non-elevator related items shall not be stored in the machine room. 9/30/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Non-elevator related items shall not be stored in the machine room. 9/30/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Fire service testing must be documented monthly. 9/30/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Fire service testing must be documented monthly. Note: Last documented test was the June 2024 annual inspection. 9/30/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Fire service testing must be documented monthly 7/16/2025
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency lighting shall work. Multi-year violaton. 9/18/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Security company monitoring elevator cab phone could not give the location of elevator. Program or repair phone to provide location. Re-inspection required 11/9/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm Bell shall work with loss of main 120v power. 9/18/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/16/2025
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/1/2021
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x Teh emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspect by 7/13/23 (30 days) 8/2/2023