A17.1-1996 : Elevators
|
3.20 - Governor rope
|
206.5 Governor Ropes
|
Yes
|
Yes
|
Governor rope has broken lays and shall be repalced
|
|
|
A17.1-1996 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
206
|
Yes
|
Yes
|
Governor Pull-through exceeds manufactures setting. Correct to 400lbs or less per manufacturer.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Elevators connected to an emergency generator shall be tested for operation on emergency power
|
8/12/2023
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
Yes
|
No
|
Standby power needs to be tested
|
|