Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.20 - Governor rope 206.5 Governor Ropes Yes Yes Governor rope has broken lays and shall be repalced
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 206 Yes Yes Governor Pull-through exceeds manufactures setting. Correct to 400lbs or less per manufacturer.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Standby power needs to be tested
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators connected to an emergency generator shall be tested for operation on emergency power 8/12/2023