Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Elevator pit lighting does not work, needs repaired 5/19/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Elevator pit lighting does not work, needs repaired 5/19/2026
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Standby power needs tested
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 206 Yes Yes Governor Pull-through exceeds manufactures setting. Correct to 400lbs or less per manufacturer.
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 206 Yes Yes Governor rope is rouged and needs replaced
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties 205 Yes Yes Safety slide does not meet minimum stopping distance. Needs to slide a minimum of 10" .
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators connected to an emergency generator shall be tested for operation on emergency power 8/12/2023