Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 10/16/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 10/16/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/5/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/30/2024
MO Minimum : Elevators (H) - Machine Rooms (H)1 Access to the machine space shall maintained in a clear and unobstructed manner. There is debris on the floor of the room leading to the machine room and blocking access to it - including broken fluorescent bulbs. 11/30/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. 11/30/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Electric photo eye re-opening device shall be operable. Re-Inspection Required (2nd Notice) 3/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x The car door light ray shall be operational. 10/28/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. The machine room door is being blocked from closing due to an excessive amount of debris on the floor of the room leading to it. 11/30/2024
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lights shall be operational. 11/30/2024
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light shall be operational. 11/30/2024