MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the currents state operating certificate shall be displayed in the elevator machine room
|
10/10/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevators connected to a standby or emergency generator shall be tested on standby or emergency power. Re-inspection required
|
2/25/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
x
|
|
Hoistway door closer spring is missing on 1st floor landing, repair door closer. Re-inspection required
|
2/25/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Hoistway door closer still needs repaired
|
11/22/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Perform the required emergency generator testing
|
3/23/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
x
|
|
Pit needs to be cleaned of hydraulic fluid. Re-inspection required
|
2/25/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit still needs to be cleaned
|
11/22/2023
|