Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Excessive leaking during 15b minute set. Repair/replace control valve 12/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Excessive leaking during 15b minute set. Repair/replace control valve 12/22/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in machine room shall be a minimum of 10 foot candles to floor
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Need code dat plate conforming to sec 8.9 12/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Need elevator prints on site 12/14/2021
MO Minimum : Elevators (I) - Pits (I)1 Need to install a non-combustible sump hole cover flush with pit floor
MO Minimum : Elevators (I) - Pits (I)8 Need to install non combustible sump hole cover, flush with pit floor
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Place current state certificate in machine room 12/14/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 1/25/2021
MO Minimum : Elevators (I) - Pits (I)8 Provide a sump hole cover per 40-05.065 1/25/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Provide machine room lighting of not less than 10ft candles measured at the floor through out the entire machine room 1/25/2021