Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x x Code # 8.6.4.20.4(a) The car won't lower and hold 125% load. Goes to pit. Car won't run with capacity. Could be drive,brake, counterweighting ? Red tag until repair. 1/6/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self-locking 8/9/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Hoist cables have 1 undersized and all oily. Need to replace all hoist cables 5/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates In case of fire don't use elevator signage needed 3/26/2024