Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair alarm bell 11/21/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Dust covers are required at all landings 8/27/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Top of hoistway has old exposed wire. Cover 8/27/2025
A17.1-2016 : Elevators 2.5 - Housekeeping 2.8.1 x Remove old and unused wire from machine room. Clean up 8/27/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Ac in machine room must have disconnect in machine room. Nec 620.22(B) 8/27/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Make fire service operational 11/21/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log posted in machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x Wisperflex comp rope cover cracked extensively thru out length. Replace 8/27/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test emergency generator 11/21/2024
conversion conversion n/a Wire ropes need to be shortened. Counterweight hit buffer on top landing. 9/13/2019