MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair alarm bell
|
11/21/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Dust covers are required at all landings
|
8/27/2025
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Top of hoistway has old exposed wire. Cover
|
8/27/2025
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
2.8.1
|
x
|
|
Remove old and unused wire from machine room. Clean up
|
8/27/2025
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Ac in machine room must have disconnect in machine room. Nec 620.22(B)
|
8/27/2025
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Make fire service operational
|
11/21/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service and document on log posted in machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
x
|
|
Wisperflex comp rope cover cracked extensively thru out length. Replace
|
8/27/2025
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Test emergency generator
|
11/21/2024
|
conversion
|
conversion
|
n/a
|
|
|
Wire ropes need to be shortened. Counterweight hit buffer on top landing.
|
9/13/2019
|