MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
x
|
|
Replace missing electric duct cover in hoistway. Re-inspection required
|
4/13/2024
|
MO Minimum : Elevators
|
(G)2-Alterations
|
8.7.2.14.2 Car Enclosure
|
x
|
|
Install alteration code data plate. Re-inspection required
|
4/13/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
x
|
|
Install wiring in electric duct in machine room. Re-inspection required
|
4/13/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
x
|
|
Provide elevator pit lighting. Re-inspection required
|
4/13/2024
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
x
|
|
Install governor rope data tag. Re-inspection required
|
4/13/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Firemans hat does not flash when machine room smoke detectors are tripped. Retest smoke detectors. Re-inspection required
|
4/13/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test elevator on emergency power with full load. Re-inspection required
|
4/13/2024
|
MO Minimum : Elevators
|
2.3 - Lighting and receptacles
|
110.27 Guarding of Live Parts NFPA 72
|
x
|
|
Car light disconnect in machine room shall be fused, externally operable, & lockable in the off position. Re-inspection required
|