Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x Install alteration code data plate. Re-inspection required 4/13/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Firemans hat does not flash when machine room smoke detectors are tripped. Retest smoke detectors. Re-inspection required 4/13/2024
MO Minimum : Elevators 2.3 - Lighting and receptacles 110.27 Guarding of Live Parts NFPA 72 x Car light disconnect in machine room shall be fused, externally operable, & lockable in the off position. Re-inspection required 4/13/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) x Install governor rope data tag. Re-inspection required 4/13/2024
MO Minimum : Elevators (A) - Hoistways (A)16 x Replace missing electric duct cover in hoistway. Re-inspection required 4/13/2024
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) x Provide elevator pit lighting. Re-inspection required 4/13/2024
MO Minimum : Elevators (H) - Machine Rooms (H)8 x Install wiring in electric duct in machine room. Re-inspection required 4/13/2024