A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection)
|
Yes
|
No
|
Fireman's hat does not flash when machine room smoke detectors are tripped. Retest smoke detectors. Re-inspection required
|
4/13/2024
|
|
A17.1-2016 : Elevators
|
3.20 - Governor rope
|
2.18.5
|
Yes
|
No
|
Install governor rope data tag. Re-inspection required
|
4/13/2024
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
Yes
|
No
|
Replace missing electric duct cover in hoistway. Re-inspection required
|
4/13/2024
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
Yes
|
No
|
Install wiring in electric duct in machine room. Re-inspection required
|
4/13/2024
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
Yes
|
No
|
Car light disconnect in machine room shall be fused, externally operated and lockable in the off position. Re-inspection required
|
4/13/2024
|
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.9
|
Yes
|
No
|
Install alteration code data plate. Re-inspection required
|
4/13/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Need to perform the following tests to complete inspection: Emergency generator power operation & fire service. Re-inspection required
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
Yes
|
No
|
Test elevator on emergency power with full load. Re-inspection required
|
4/13/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency alarm in car did not work. Re-inspection required
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
Emergency light in car did not work. Re-inspection required
|
|