Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.20 - Governor rope 2.18.5 x Install governor rope data tag. Re-inspection required 4/13/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Test elevator on emergency power with full load. Re-inspection required 4/13/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) x Fireman's hat does not flash when machine room smoke detectors are tripped. Retest smoke detectors. Re-inspection required 4/13/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Replace missing electric duct cover in hoistway. Re-inspection required 4/13/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Install wiring in electric duct in machine room. Re-inspection required 4/13/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Car light disconnect in machine room shall be fused, externally operated and lockable in the off position. Re-inspection required 4/13/2024
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 x Install alteration code data plate. Re-inspection required 4/13/2024