Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 Yes No Car light disconnect in machine room shall be fused, externally operated and lockable in the off position. Re-inspection required 4/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm in car did not work. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light in car did not work. Re-inspection required
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) Yes No Fireman's hat does not flash when machine room smoke detectors are tripped. Retest smoke detectors. Re-inspection required 4/13/2024
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 Yes No Install alteration code data plate. Re-inspection required 4/13/2024
A17.1-2016 : Elevators 3.20 - Governor rope 2.18.5 Yes No Install governor rope data tag. Re-inspection required 4/13/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No Install wiring in electric duct in machine room. Re-inspection required 4/13/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to perform the following tests to complete inspection: Emergency generator power operation & fire service. Re-inspection required
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No Replace missing electric duct cover in hoistway. Re-inspection required 4/13/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Test elevator on emergency power with full load. Re-inspection required 4/13/2024