Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Recovery pump for the hydraulic oil in the elevator pit not allowed per memo from the state, memo 006 A17.1 8.6.5.5
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit, oil collection line had fallen out of the collection bucket, oil on the pit floor. 7/14/2021
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 recovery pump in the elevator pit is not allowed per state of Missouri memo 006, replace with a bucket 10/26/2023
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Adjust the door restrictor so it works 11/4/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x the overspeed valve is installed backwards and needs to be installed correctly and tested. 8/17/2021
A17.1-1996 : Elevators 2.35 - Supply Line and Shutoff Valve 303 replace vic couplers in the tank that are leaking oil durring normal operation 1/10/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Perform monthly fire service test and post a log in the machine room 7/21/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The state operating certificate posted in the machine room is to be updated every year 5/18/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 7/14/2021