A17.1-1996 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
303
|
|
|
replace vic couplers in the tank that are leaking oil durring normal operation
|
1/10/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
Perform monthly fire service test and post a log in the machine room
|
7/21/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The state operating certificate posted in the machine room is to be updated every year
|
5/18/2022
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Adjust the door restrictor so it works
|
11/4/2024
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
recovery pump in the elevator pit is not allowed per state of Missouri memo 006, replace with a bucket
|
10/26/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Recovery pump for the hydraulic oil in the elevator pit not allowed per memo from the state, memo 006 A17.1 8.6.5.5
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
7/14/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit, oil collection line had fallen out of the collection bucket, oil on the pit floor.
|
7/14/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
the overspeed valve is installed backwards and needs to be installed correctly and tested.
|
8/17/2021
|