Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.35 - Supply Line and Shutoff Valve 303 No No replace vic couplers in the tank that are leaking oil durring normal operation 1/10/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No Perform monthly fire service test and post a log in the machine room 7/21/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The state operating certificate posted in the machine room is to be updated every year 5/18/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No Adjust the door restrictor so it works 11/4/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph No No Provide fire egress signage at the 2nd floor 7/18/2025
A17.1-2016 : Elevators 9.19 - Maintenance Records 8.6.1.4 Maintenance Records No No Provide updated maintenance task log 7/18/2025
A17.1-2016 : Elevators 1.7 - Car door or gate 8.6.4.13.1 Door Systems General No No Replace worn car door rollers 7/18/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Remove oil absorbent pads from the pit floor 7/18/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Remove scavenger unit from the pit 7/18/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Provide updated permit in the cab or other specified location 7/18/2025
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 No No recovery pump in the elevator pit is not allowed per state of Missouri memo 006, replace with a bucket 10/26/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Recovery pump for the hydraulic oil in the elevator pit not allowed per memo from the state, memo 006 A17.1 8.6.5.5 10/24/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 7/14/2021
MO Minimum : Elevators (I) - Pits (I)1 No No Clean the pit, oil collection line had fallen out of the collection bucket, oil on the pit floor. 7/14/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No the overspeed valve is installed backwards and needs to be installed correctly and tested. 8/17/2021