MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
No
|
No
|
Clean unexposed hoistway sills
|
7/18/2025
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
Yes
|
Yes
|
adjust nudging speed, doors will not close when keyed off of fire service phase 2 to return to the recall floor
|
8/30/2022
|
|
A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
1001.2(a)(15)
|
No
|
No
|
In case of fire use stairs signs missing on top and bottom landings
|
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
No
|
No
|
Machine room fire extinguisher inspection tag is expired, it was due for annual inspection in February 2026.
|
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
No
|
No
|
Clean up oil on pit floor
|
|
|
A17.1-1996 : Elevators
|
5.11 Plunger and Cylinder
|
1206.5b(5) Oil Leakage Collection
|
No
|
No
|
Jack head drain is clogged with lint and the oil is overflowing the head and running down the side of the jack.
|
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
No
|
No
|
Perform monthly fire service test and post a log in the machine room
|
7/21/2020
|
|
A17.1-1996 : Elevators
|
1.14 - Ventilation
|
204.2c
|
No
|
No
|
repair duct work for car top a/c unit, ensure the a/c unit is in working order, glass back elevator exposed to direct sunlight
|
7/21/2020
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
No
|
No
|
repair elevator cab lights, they are not staying on
|
1/10/2020
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
replace the emergency phone, it did not work and the phone line tested good
|
3/18/2020
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
the state operating certificate in the machine room is to be updated every year
|
5/31/2022
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
7/14/2021
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Provide updated permit in the cab or other specified location
|
7/18/2025
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
Yes
|
No
|
Elevator would not return to recall floor when the phase 2 was turned off
|
2/26/2025
|
|
A17.1-2016 : Elevators
|
1.14 - Ventilation
|
8.11.3.1.1(n)
|
No
|
No
|
make sure a/c unit on the car top is in working order
|
5/31/2022
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
No
|
No
|
Provide updated maintenance task log
|
7/18/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
the fire service phase 2 keyswitch collar markings cannot be read, replace collar
|
5/31/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
in car stop keyswitch collar marking cannot be read, replace collar
|
5/31/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
No
|
No
|
Clean off car top, air conditioning unit that hasn't worked for years should be replaced with something that works. (glass back elevator)
|
10/24/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
No
|
No
|
Clean the car top
|
7/18/2025
|