Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) Yes No Adjust car door force to be 30 lbs or less 5/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No can not read the markings on the fire service phase 2 keyswitch collar, replace the collar 5/31/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No can not read the markings on the in car stop keyswitch collar, replace the stop switch collar 5/31/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean off car top, air conditioning unit that hasn't worked for years should be replaced with something that works. (glass back elevator) 10/24/2024
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems No No Clean the unexposed hoistway sills 7/18/2025
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Clean up oil in pit after replacing the packing
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No emergency light did not come on, the alarm bell did work 5/31/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No emergency lights did not come on, repair emergency lights 3/13/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No Emergency lights did not work even with new battery, repair wiring to the emergency lights
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) No No In case of fire use stairs signs missing on top and bottom landings
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No Machine room fire extinguisher inspection tag is expired, it was due for annual inspection in February 2026.
A17.1-2016 : Elevators 5.15 - Overspeed Valve 3.19.4.7.5(a) Yes No Overspeed valve lock nut can not be broke loose to adjust the valve, replace the overspeed valve, and perform reinspection
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) Yes No Packing gland blew during pressure test, replace packing
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No Perform monthly fire service test and post a log in the machine room 7/21/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No Provide updated maintenance task log 7/18/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Remove unexposed oil absorbent pads from the pit floor 7/18/2025
A17.1-1996 : Elevators 1.14 - Ventilation 204.2c No No repair car top a/c unit, it is in peices, needs to work for glass back elevator exposed to direct sunlight 7/21/2020
A17.1-2016 : Elevators 2.34 - Flexible Hydraulic Hose and Fitting Assemblies 8.11.3.1.2(v) No No Repair oil cooler system leak in the equipment room and clean oil from floor 7/18/2025
A17.1-1996 : Elevators 1.14 - Ventilation 204.2c No No the air conditioner provided for this observation elevator is not working, there shall be a minimum air handling capacity to provide one air change per minute based on net inside car volume, with auxiliar power source 10/24/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 7/14/2021
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No the emergency light battery is dead and needs to be replaced 1/10/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No the state operating certificate in the machine room is to be updated every year 5/31/2022
A17.1-2016 : Elevators 1.14 - Ventilation 8.11.3.1.1(n) No No top of car air condition unit is not in working order, repair a/c unit 5/31/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Water on the machine room floor after storm, repair leak 10/24/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - No No when fire service phase 2 was keyed to the off position with the doors open at a floor other than the designated level, the elevator did not go back on phase 1 and return to the designated level 1/9/2020