Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)3 Bottom floor sill bowed not allowing hoistway door to be self closing 10/23/2019
MO Minimum : Elevators (A) - Hoistways (A)3 First Floor Hoistway sill is bowed preventing unassisted closing of hoistway door 8/8/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Alarm bell in car does not work 8/8/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Emergency light in car doesn't work 10/23/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x A17.1 1984 Rule 110.11e - Hoistway door panels shall not have a gap larger than 3/8" between the door and frame. 8/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6.
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine Room is not to contain any items not related to the operation of the elevator 8/8/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 Multiple exposed wires running through machine room 10/23/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self closing and self locking 10/23/2019
MO Minimum : Elevators (N) - Guide Rails (N)1 Reduced running clearance. Elevator door clutch scrapes fascia when running up. Check guide rails for adjustment. 1/15/2021