Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)13 Hoistway needs to be fully enclosed. Opening at front top of hoistway needs to be sealed. 1/2/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Door knob needs to be self locking on Elevator equipment room 1/2/2024
MO Minimum : Elevators (I) - Pits (I)5 Repair or replace pit ladder
A17.1-1996 : Elevators 3.10 - Hoistway construction 1001.2(c)(16) Large piece of sheetrock in hoistway at the top of the shaft needs to be replaces.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.5 Illuminated Visual Signal x Must Make Phase I Visual Signal Operable. 2.27.3.1.(h) 2/5/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) Must make both Audible and Visual signal operable. 8/18/2023
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 Must replace missing Sheetrock above top landing in hoistway to maintain encloser full height of hoisway.
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must Post Current State operating Cert. In Mach. Room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Need Phase I Fire Service Operating instructions replaced. Can not read them anymore 1/2/2024
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 x Must provide Alteration Code Data Plate. 8.9.1 2/5/2025