Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The auxiliary power lowering (UPS Unit) shall be operational. Note: The 11/11/24 re-inspection was only to test the phone.
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x The auxiliary power lowering (UPS Unit) shall be operational. 5/5/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The auxiliary power lowering (UPS Unit) shall be operational. 11/11/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall be operational on main and auxiliary power. 11/11/2024