MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
No
|
No
|
Sump pump wiring shall be protected against damage. SO cord running along wall suppling 120 volts does not meet NFPA 70.
|
8/10/2022
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
3.26.10
|
Yes
|
No
|
Standby power selection operation not working correctly, battery lowering is not working. Re-inspection required
|
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
Yes
|
No
|
Heat detector at the top of the hoistway shall be located not more than 24" from the sprinkler head. NFPA 72 Did not red tag unit.
|
3/1/2022
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Car Gate reopening device does not work.
|
2/12/2020
|