Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)8 No No Sump pump wiring shall be protected against damage. SO cord running along wall suppling 120 volts does not meet NFPA 70. 8/10/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 Yes No Standby power selection operation not working correctly, battery lowering is not working. Re-inspection required
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Heat detector at the top of the hoistway shall be located not more than 24" from the sprinkler head. NFPA 72 Did not red tag unit. 3/1/2022
conversion conversion n/a No No Car Gate reopening device does not work. 2/12/2020