Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage Yes No Hoses going back to the tank from the Hydraulic cylinder shall be removed, and means to collect oil shall be provided in the elevator pit.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No No maintenance control program. 6/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Water is in the pit. 6/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.1 - Top-of-car stop switch 8.11.2.1.3(a) No No Switch blew a fuse during test. REINSPECTION REQUIRED. 6/16/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working. Re-insepection required 5/29/2025