Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.32 - Control Valve 1004.2(b)(15) Elevator failed leak down test. Control valve allowed the car to drift down 2" in 15 minutes. 8.11.3.2.2 9/8/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Provide existing pit light to work. 6/27/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Electrical pipe supplying pit light not attached to wall, make so. 6/27/2023
MO Minimum : Elevators (I) - Pits (I)8 Provide Code compliant sump hole cover in the pit. 6/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Clean the pit. 6/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces Observed black mold on machine room wall, abate as needed. 6/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces Observed pipe leaking/dripping onto machine room floor. Repair pipe as needed. 6/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces Seal the hole in the ceiling of the machine room, after leak has been fixed. 6/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide Code compliant fire extinguisher in the elevator machine room. 6/27/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post Phase I instructions near f/f switch in the lobby. 6/27/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post Phase II instructions in the car, near f/f switch. 6/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Provide MCP. 6/27/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide existing battery backup lowering unit to work correctly. 3/1/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Observed smoke detector missing from elevator lobby. 14 days to repair and retest for proper operation. 3/1/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Observed heat detector in the machine room is more than 24” away from sprinkler. Repair as needed. 3/1/2024