A17.1-1996 : Elevators
|
2.32 - Control Valve
|
1004.2(b)(15)
|
|
|
Elevator failed leak down test. Control valve allowed the car to drift down 2" in 15 minutes. 8.11.3.2.2
|
9/8/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Provide existing pit light to work.
|
6/27/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Electrical pipe supplying pit light not attached to wall, make so.
|
6/27/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Provide Code compliant sump hole cover in the pit.
|
6/27/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
Clean the pit.
|
6/27/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
|
|
Observed black mold on machine room wall, abate as needed.
|
6/27/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
|
|
Observed pipe leaking/dripping onto machine room floor. Repair pipe as needed.
|
6/27/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
|
|
Seal the hole in the ceiling of the machine room, after leak has been fixed.
|
6/27/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Provide Code compliant fire extinguisher in the elevator machine room.
|
6/27/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post Phase I instructions near f/f switch in the lobby.
|
6/27/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post Phase II instructions in the car, near f/f switch.
|
6/27/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests)
|
|
|
Provide MCP.
|
6/27/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide existing battery backup lowering unit to work correctly.
|
3/1/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Observed smoke detector missing from elevator lobby. 14 days to repair and retest for proper operation.
|
3/1/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Observed heat detector in the machine room is more than 24” away from sprinkler. Repair as needed.
|
3/1/2024
|