Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Re-inspection is required. 12/21/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The hydraulic oil cooler that is installed in the machine room has been switched off. This device cools the temperature of the oil when the elevator is being used excesively. It may be noted, that the elevator would not perform multiple runs at 100% capacity for the requried five year full load test. The building occupancy at this time is not at or near capacity at this time, which would require the elevator to perform at 100% capacity. Recmomment continual monitoring of the oil temperature and reactivate the oil cooler. 1/15/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The hydraulic oil cooler that is installed in the machine room has been switched off. This device cools the temperature of the oil when the elevator is being used excessively. It may be noted, that the elevator would not perform multiple runs at 100 % capacity for the required five year full load test. The building occupancy at this time is not at or near capacity at this time, which would require the elevator to perform at 100% capacity. Recommend continual monitoring of the oil temperature and reactivate the oil cooler. 1/15/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. 1/7/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. 2/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. 2/15/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)11 The dead end hitch for the hoisting rope has one securing clip missing in the pit. Attach clip to retain the rope properly in the wedge shackle. 2/15/2023
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 The hydraulic oil cooler that is installed in the machine room has been switched off. This device cools the temperature of the oil when the elevator is being used excessively. It may be noted, that the elevator would not perform multiple runs at 100 % capacity for the required five year full load test. The building occupancy at this time is not at or near capacity at this time, which would require the elevator to perform at 100% capacity. Recommend continual monitoring of the oil temperature and the oil cooler shall be reactivated. 1/7/2021
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 The hydraulic oil cooler that is installed in the machine room has been switched off. This device cools the temperature of the oil when the elevator is being used excessively. It may be noted, that the elevator would not perform multiple runs at 100 % capacity for the required five year full load test. The building occupancy at this time is not at or near capacity at this time, which would require the elevator to perform at 100% capacity. Recommend continual monitoring of the oil temperature and the oil cooler shall be reactivated. 2/20/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 The hydraulic oil cooler that is installed in the machine room has been switched off. This device cools the temperature of the oil when the elevator is being used excessively. It may be noted, that the elevator would not perform multiple runs at 100 % capacity for the required five year full load test. The building occupancy at this time is not at or near capacity at this time, which would require the elevator to perform at 100% capacity. Recommend continual monitoring of the oil temperature and the oil cooler shall be reactivated. 11/1/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Upon activation of fireman’s emergency service phase I, the elevator car returned to the primary floor as required BUT DID NOT open the rear opening where the fireman’s phase I key is located. This shall be corrected to open the rear door where the key switch is to comply with installation code. Reinspection required in 30 days. 1/7/2021