MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Main hoist ropes rouged and undersized.
|
1/27/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Main hoisting ropes rouged, and undersized.
|
2/1/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
|
|
Emergency phone working, but not identifying location.
|
2/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.2.7
|
x
|
|
Emergency power not tested at time of inspection.
|
2/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
6th floor landing door has worn gib.
|
2/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working.
|
2/9/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.2.7
|
x
|
|
Standby power not tested at time of inspection.
|
2/9/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Provide an up to date fire extinguisher in machine room.
|
2/29/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide an MCP in machiner room.
|
2/29/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
2/29/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.11.1 Firefighters' Emergency Operation & Documentation
|
|
|
Provide FFS testing log in machine room.
|
2/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
Provide type ABC fire extinguisher in machine room.
|
2/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide MCP in machine room.
|
2/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
2/29/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
2/29/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Car selector on cartop needs new guides.
|
5/20/2024
|
MO Minimum : Elevators
|
(J) - Counterweights
|
(J)2
|
|
|
Counterweight rollers worn, replace.
|
5/20/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Floor 4 landing door missing one gib.
|
7/15/2024
|