A17.1-1996 : Elevators
|
3.9 - Floor and emergency identification numbering
|
100.7
|
|
|
Label inside of hoistway doors with a numeral
|
11/6/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell does not operate
|
3/3/2021
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Machine room access door shall be self-locking and non-defeatable
|
12/8/2022
|
A17.1-1996 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
102
|
|
|
Install cover over car door operator electrical control board.
|
12/8/2022
|
A17.1-1996 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
102
|
|
|
Install cover on electrical wire trough located on top of the elevator
|
12/8/2022
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light does not operate
|
3/3/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
12/14/2023
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
215
|
|
|
Need to post code data plate on controller or mainline disconnect. Elevator installed 2001.
|
7/1/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current state operating certificate not displayed in machine room
|
11/6/2023
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
Post In Case of Fire signage next to hall button fixture at each landing
|
11/6/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Remove rag box, and debris from cartop.
|
7/1/2020
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
Scavenger pump in pit pumps oil to hydraulic tank in machine room. Need to remove scavenger pump.
|
7/1/2020
|
conversion
|
conversion
|
n/a
|
|
|
Install duct cover on wire raceway in machine room.
|
7/1/2020
|