Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate not displayed in machine room 11/6/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate 3/3/2021
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light does not operate 3/3/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 12/14/2023
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 Install cover on electrical wire trough located on top of the elevator 12/8/2022
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 Install cover over car door operator electrical control board. 12/8/2022
conversion conversion n/a Install duct cover on wire raceway in machine room. 7/1/2020
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 100.7 Label inside of hoistway doors with a numeral 11/6/2023
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room access door shall be self-locking and non-defeatable 12/8/2022
A17.1-1996 : Elevators 2.14 - Code data plate 215 Need to post code data plate on controller or mainline disconnect. Elevator installed 2001. 7/1/2020
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 Post In Case of Fire signage next to hall button fixture at each landing 11/6/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Remove rag box, and debris from cartop. 7/1/2020
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Scavenger pump in pit pumps oil to hydraulic tank in machine room. Need to remove scavenger pump. 7/1/2020