Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 3/1/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Fire extinguisher is still out of date 3/1/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No The fire extinguisher has no certification tag. 3/1/2026
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No Fire extinguisher does not have a date tag. 3/1/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/1/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Operating certificate shall be posted in machine room. 3/1/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit shall be kept clean and dry. Past Water shows at least 2 feet high. 3/1/2026
A17.1-2016 : Elevators 4.5 - Access to Hoistway 2.12.7 No No Hoistway Access Keyswitch shall work at top and bottom landings.
A17.1-2016 : Elevators 3.28 - Counterweight and counterweight buffer 8.7.2.4 Yes No Counterweight roller guides have been exposed to water and are rusty. Shall be replaced. 2/26/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Yes No Repair or replace rusty buffer springs. 3/1/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Yes No repair or replace rusty pit channel 3/1/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Yes No repair or replace rusty governor tail sheave 3/1/2026
A17.1-2016 : Elevators 3.20 - Governor rope 8.10.3.2.3(u) Yes No Governor rope has been exposed to water and is rusty. Shall be replaced. 30 days. 2/26/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair inoperable emergency phone. 2/17/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) Yes No Machine room wiring shall be enclosed. 7/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Yes No The machine room lighting shall not be less than 19fc at the floor level. 7/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) Yes No An ABC type fire extinguisher shall be provided in the elevator machine room. 7/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.1 - Car platform guard 8.11.2.1.4(a) Yes No Car platform guard shall be 48". 7/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Yes No Provide temperature and humidity control. 7/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) Yes No Provide counterweight runby signage. Signage shall be 1" stamped, etched, or cast lettering. 7/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 8.11.2.1.2(d) Yes No Seal all machine room penetrations. 7/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) Yes No Seal all hoistway penetrations. 7/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Yes No Provide code compliant pit lighting. 7/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) Yes No Adjust bottom hoistway access. 7/6/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 1/16/2023