A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair inoperable emergency phone.
|
2/17/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
1/16/2023
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Fire extinguisher does not have a date tag.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
x
|
|
Provide code compliant pit lighting.
|
7/6/2021
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
x
|
|
The machine room lighting shall not be less than 19fc at the floor level.
|
7/6/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
8.11.2.1.2(d)
|
x
|
|
Seal all machine room penetrations.
|
7/6/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
8.11.2.1.2(f)
|
x
|
|
Provide temperature and humidity control.
|
7/6/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
x
|
|
An ABC type fire extinguisher shall be provided in the elevator machine room.
|
7/6/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
8.11.2.1.2(h)
|
x
|
|
Machine room wiring shall be enclosed.
|
7/6/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.1 - Car platform guard
|
8.11.2.1.4(a)
|
x
|
|
Car platform guard shall be 48".
|
7/6/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.11.2.1.4(e)
|
x
|
|
Adjust bottom hoistway access.
|
7/6/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.8 - Hoistway enclosure
|
8.11.2.1.4(h)
|
x
|
|
Seal all hoistway penetrations.
|
7/6/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.11.2.1.5(b)
|
x
|
|
Provide counterweight runby signage. Signage shall be 1" stamped, etched, or cast lettering.
|
7/6/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher is still out of date
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
The fire extinguisher has no certification tag.
|
|