conversion
|
conversion
|
conversion - reinspect
|
Yes
|
No
|
Replace undersized wire ropes.
|
4/12/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
Yes
|
Yes
|
Drive machine sheave liner is damaged and falling off traction sheave, needs repaired. Red-tagged and removed from service. Re-inspection required before use.
|
6/5/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Category 5 test incomplete, perform the following tests to complete inspection: test car safeties at rated speed with rated load, test car buffer at rated speed with rated load, test counterweight buffer at rated speed, test brake with 125% of rated load, test governor switch and governor jaw tripping speed, test governor rope pull through and pull out force. Re-inspection required
|
6/5/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Standby Power shall be tested
|
|