Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Replace undersized wire ropes. | 4/12/2019 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Category 5 test incomplete, perform the following tests to complete inspection: test car safeties at rated speed with rated load, test car buffer at rated speed with rated load, test counterweight buffer at rated speed, test brake with 125% of rated load, test governor switch and governor jaw tripping speed, test governor rope pull through and pull out force. Re-inspection required | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | x | x | Drive machine sheave liner is damaged and falling off traction sheave, needs repaired. Red-tagged and removed from service. Re-inspection required before use. |